MUK HIU is a Revit add-in for sizing and checking low-temperature hot-water (LTHW) pipework in heat networks and communal heating systems, from the plant room to each heat interface unit (HIU). The Autodesk Marketplace listing says its calculations follow CIBSE DS 439, also identified there as CP1 Heat Networks: Code of Practice for the UK.

How the network calculation works

Select a pipe to start. MUK HIU traces the flow and return pipework, finds the HIUs and totals the loads downstream of each pipe. It applies the selected diversity settings to those loads.

For domestic hot water, the listing gives the DS 439 diversity factor as k = 0.0316 + 0.5 × N−0.5 + 0.468 × N−1. For space heating, users can choose a fixed percentage or the variable factor 0.62 + 0.38/N. The flow and return calculations use separate water temperatures, with design ΔT derived from the supply and return temperatures. Pressure loss uses Darcy-Weisbach with the Haaland friction factor, 64/Re for laminar flow, and an optional allowance for fittings.

Checks and results

  • Check compares drawn pipe sizes with the maximum velocity and pressure loss per metre set for the project.
  • Size assigns each flow and return pipe the smallest size that meets those limits. The default minimum is DN15.
  • Index circuit identifies the most unfavourable HIU circuit, adds its flow, HIU pressure drop and return losses, and shows pump duty as flow rate and head.
  • Loss map colours pipes green, amber or red according to pressure loss per metre.
  • MUK DS439 panel shows results for a selected pipe, fitting or HIU. Its table can select every model section that includes the chosen pipe.
  • PDF report includes design criteria, building and level loads, HIU and pipe schedules, the index circuit, pump duty, static pressure and system water content. The report also includes three 3D views drawn from the model: flow and return, the index circuit and the pressure-loss map.

Model changes and engineering checks

MUK HIU runs separately from Revit's own pipe calculations. Pipe sizes change in the model when you run Size. If a diameter change disconnects valves or fittings, the add-in attempts to reconnect them and reports how many; inspect those connections afterward.

Height differences are excluded from the pressure calculation, while static pressure is reported separately. The listing says a competent heating engineer should check the results before they are used.

Trial, sample model and support

The Marketplace listing shows a 30-day free trial followed by an annual subscription at $299 per year. It includes a sample model with 12 HIUs across three levels and a MUK_HIU valve family with 13 types. The listing also says project data is shared with MUK GAS for the report header, and that the licence check sends only your Autodesk user ID to Autodesk.

For support, Monso MEP Engineering UK Ltd lists [email protected] and says it replies within two working days. Include your Revit version and a screenshot of the MUK DS439 panel; attach the PDF report if possible.